Hardware Ref, Installation, and Troubleshooting User guide

2Ć2
Table 2.1 Ć P
ower and NEMA Enclosure Ratings
Model
Number
Selected
Regulation* and
Horsepower Rating
Input
Voltage
(+/- 10%)
NEMA
Rating
Input
KVA
Input
Amps
Output
Amps
at 8 kHz
Power
Loss W
atts
(F
ull Load)
1V4150
1V4450
V/Hz
or V
ector
(1 HP)
380-460 VAC 1
4X/12
2.0 2.5 2.1 60
2V4150
2V4450
V/Hz or Vector
(2 HP)
380-460 VAC 1
4X/12
3.3 4.2 3.4 100
3V4150
3V4450
V/Hz or Vector
(3 HP)
380-460 VAC 1
4X/12
5.1 6.4 5.3 140
5V4150
5V4450
V/Hz or Vector
(5 HP)
380-460 VAC 1
4X/12
7.9 9.9 8.2 180
7V4150
7V4250
V/Hz or Vector
(7.5 HP)
380-460 VAC 1
12
10.7 13.4 11.1 210
10V4150
10V4250
V/Hz or Vector
(10 HP)
380-460 VAC 1
12
13.4 16.8 14.2 250
15V4150
15V4250
V/Hz or Vector
(15 HP)
380-460 VAC 1
12
20.2 25.4 21.0 375
20V4150
20V4250
V/Hz or Vector
(20 HP)
380-460 VAC 1
12
26.1 32.7 27.0 600
25G4150
25G4250
V/Hz
(25 HP)
380-460 VAC 1
12
29.5 37.0 30.4 600
25V4150
25V4250
V/Hz or Vector
(25 HP)
380-460 VAC 1
12
30.2 38.0 34.5 750
30V4150
30V4250
V/Hz or Vector
(30 HP)
380-460 VAC 1
12
35.0 44.0 39.0 800
40V4150
40V4250
V/Hz or Vector
(40 HP)
380-460 VAC 1
12
46.2 58.0 54.0 960
50V4150
50V4250
V/Hz or Vector
(50 HP)
380-460 VAC 1
12
57.3 72.0 67.0 1200
50R4150 V
ector (50 HP)
V/Hz (75 HP)
380-460 VAC 1 65.0
81.0
81.0
102
70.0**
90.0**
1420
60G4150
60G4250
V/Hz
(60 HP)
380-460 VAC 1
12
71.7 90.0 78.0 1200
75R4150 Vector (60-75 HP)
V/Hz (100 HP)
380-460 VAC 1 80.0
100
101
126
89.0**
116**
1400
1780
125R4150 Vector (100-125 HP)
V/Hz (125-150 HP)
380-460 VAC 1 127
170
159
213
152**
210**
2410
3200
ă*With V/Hz regulation, 110% continuous output current capability. With vector regulation, 150% output current capability for one
minute.
**At 2 kHz. For 4 kHz operation, derate by 20%. For 8 kHz operation, derate by 40%.
2.2 NEMA Enclosures
Each of the GV3000 P
ower Modules have one of following NEMA ratings:
D
NEMA 1:
V
ented. Contains a communication access door that allows access to the
communication port without removing the cover
. Intended for generalĆpurpose indoor
applications.
D NEMA 4X/12:
Not vented. Supplied with base and keypad gaskets. Intended for use in indoor
environments that require a water
Ćtight/dust
Ćtight enclosure. An enclosure with this
NEMA rating encompasses both ratings (4X and 12).
D
NEMA 12: Intended for use in indoor environments that require a dust
Ćtight/dripĆtight enclosure.
See table 2.1 for a listing of the P