Hardware Ref, Installation, and Troubleshooting User guide

3Ć1
3.0 PLANNING BEFORE INSTALLING
This
chapter provides information that must be considered when planning a GV3000 drive
installation. Installation site requirements, drive requirements, and wiring requirements are presented.
DANGER
ONLY QUALIFIED ELECTRICAL PERSONNEL FAMILIAR WITH THE CONSTRUCTION AND
OPERATION OF THIS EQUIPMENT AND THE HAZARDS INVOLVED SHOULD INSTALL, ADJUST,
OPERATE,
OR SERVICE THIS EQUIPMENT
. READ AND UNDERST
AND THIS MANU
AL AND
OTHER
APPLICABLE
MANU
ALS IN THEIR ENTIRETY BEFORE PROCEEDING. F
AIL
URE TO OB
SERVE THIS
PRECAUTION COULD RESULT IN SEVERE BODIL
Y INJURY OR L
OS
S OF LIFE
.
DANGER
THE
USER IS RESPONSIBLE FOR CONFORMING WITH ALL APPLICABLE L
OCAL
, NA
TIONAL,
AND
INTERNATIONAL CODES. WIRING PRACTICES, GROUNDING, DISCONNECTS, AND
OVERCURRENT PROTECTION ARE OF PARTICULAR IMPORTANCE. FAILURE TO OBSERVE THIS
PRECAUTION COULD RESULT IN SEVERE BODIL
Y INJURY OR L
OS
S OF LIFE
.
CAUTION:
U
se
o
f p
owe
r c
orrectio
n c
apacitor
s o
n t
h
e o
utpu
t o
f t
h
e d
riv
e c
a
n r
esul
t i
n e
rrati
c o
peratio
n o
f t
he
motor,
n
uisanc
e t
ripping
, a
nd/o
r p
ermanen
t d
amag
e t
o t
h
e d
rive
. R
emov
e p
owe
r c
orrectio
n c
apacitor
s b
efore
proceeding. Failur
e t
o o
bserv
e t
his precautio
n c
ould resul
t i
n damag
e t
o o
r destructio
n o
f t
h
e e
quipment.
3.1 Requirements for the Installation Site
It
is important to properly plan before installing a GV3000 drive to ensure that the drive's environment
and operating conditions are satisfactory
. Note that no devices are to be mounted behind the drive.
This area must be kept clear of all control and power wiring. Read the following recommendations
before continuing with drive installation.
3.1.1 Making Sure Environmental Conditions are Met
Before
deciding on an installation site, consider the following guidelines:
D V
erify that NEMA 1 drives can be kept clean, cool, and dry
.
D
The area chosen should allow the space required for proper air flow as defined in section 3.1.2.
D
Be sure that NEMA 1 drives are away from oil, coolants, or other airborne contaminants.
D
Do not install the drive above 1000 meters (3300 feet) without derating output power
. F
or every
91.4 meters (300 feet) above 3300 feet, derate the output current 1%.
D V
erify that the drive location will meet the environmental conditions specified in table 3.1.
T
able 3.1 Ć Ambient Conditions
Condition Specification
Operating T
emperature (Ambient)
0r to +40r C (32r to 104rF)
Storage T
emperature (Ambient)
-40rāto +65rC (-40r to +149rF)
Humidity
5 to 95% (nonĆcondensing)