Hardware Ref, Installation, and Troubleshooting User guide
3Ć7
GV3000
Drive
Motor
38
m (125')
38 m (125')
15 m (50')
60 m (200')
60 m (200')
8 m (25') 8 m (25')
76 m (250')
GV3000
Drive
GV3000
Drive
GV3000
Drive
Motor
Motor
Motor
Motor Motor
Motor
Figure 3.3 Ć Single and Multiple Motor Lead Lengths
3.2.2.5 Recommended
Serial Communication Cable Lengths
Connector J8 on the Regulator boards is an RS
Ć232 serial communication port. This connector
allows the GV3000 drive to communicate with external devices such as a personal computer using
RSĆ232 protocol. See table A
.5. T
wo RSĆ232 cables are available from Reliance: a 3.5 meter (12 feet)
DĆshell 9Ćpin to 9Ćpin cable (M/N 615184Ć1A) and a 0.3 meter (1 foot) DĆshell 9Ćpin to 25Ćpin adaptor
cable (M/N 615184Ć2A). User
Ćconstructed cables can be up to 15 meters (50 feet) in length. Note that
for communication between a GV3000 drive and a personal computer
, the Control and Configuration
software must also be used. Refer to instruction manual D2Ć3348 for more information.
The Regulator boards have one set of RS
Ć232 transmit/receive lines. These lines can be accessed by
only one
device at a time: connector J8, the RS
Ć232 terminals (1Ć3) on the terminal strip, or an
Operator Interface module (OIM).
3.2.3 Selecting Input Line Branch Circuit Fuses
CAUTION:
The NEC/CEC requires
that upstream branch circuit protection be provided to protect input pow
Ć
er
wiring. Install the fuses recommended in table
3.9. Do not exceed the fuse ratings. F
ailure to observe this
precaution
could result in damage to or destruction of the equipment.
Input line branch circuit protection fuses must be used to protect the input power lines. See figures
5.1 and 5.2. Recommended fuse values are shown in table 3.9. The input fuse ratings listed in table
3.9 are applicable for one drive per branch circuit. No other load may be applied to that fused circuit.