Hardware Ref, Installation, and Troubleshooting User guide
3Ć8
Table 3.9 Ć AĆC Input Line F
use Selection V
alues
Model
Number
Horsepower Rating Input Voltage Fuse Rating*
1V4150
1V4450
1 380Ć460 VAC 6A
2V4150
2V4450
2 380Ć460 VAC 8A
3V4150
3V4450
3 380Ć460 VAC 12A
5V4150
5V4450
5 380Ć460 VAC 20A
7V4150
7V4250
7.5 380Ć460 VAC 25A
10V4150
10V4250
10 380Ć460 VAC 35A
15V4150
15V4250
15 380Ć460 VAC 45A
20V4150
20V4250
20 380Ć460 VAC 60A
25G4150
25G4250
25 380Ć460 VAC 70A
25V4150
25V4250
25 380Ć460 VAC 70A
30V4150
30V4250
30 380Ć460 VAC 100A
40V4150
40V4250
40 380Ć460 VAC 100A
50V4150
50V4250
50 380Ć460 VAC 125A
50R4150 V
ector 50
V/Hz 75
380Ć460 VAC 125A
60G4150
60G4250
60 380Ć460 VAC 150A
75R4150 Vector 60Ć75
V/Hz 100
380Ć460 VAC 125A
150A
125R4150 Vector 100Ć125
V/Hz 125Ć150
380Ć460 VAC 250A
*Recommended fuse type: UL Class J, 600V, time delay, or equivalent.
3.2.4 Meeting Pulse Tachometer Specifications (Vector Regulation Only)
GV3000
drives set up for vector regulation require a pulse tachometer for closed loop operation.
P
ulse tachometer specifications are provided in table A
.6. Drives set up for volts/hertz regulation do
not require a pulse tachometer for feedback because they operate in the open loop mode.
3.2.5 Verifying Power Module Output Current Rating is Greater Than Motor Full Load
Amps
Verify
that the GV3000 output current rating is greater than the motor's full load current (amps).
T
able 2.1 lists the output current values.