Wiring Analog Outputs
10
11
0Ć10 VDC or 4Ć20 mA
Analog Output Reference
Regulator Common
The setting of parameter P
.012 selects the terminal strip
analog output source (either speed or torque). Jumper J17
must also be set. See figure 2.11. The 4Ć20mA current
selection requires a power supply for operation. The power
can be sourced from the pulse tachometer supply, terminal
4 (15VDC), or from an external 15V power supply
. Note that
the maximum supply current from terminal 4 is 250mA
(pulse tachometer and current source) at 15V
. T
erminals 9
and 11 are internally connected.
Terminal
Strip
+
Ċ
+
Ċ
+
Ċ
Load
(Meter or Analog Input)
Connection to the negative side of the
power supply is only required
when an external 15V power supply is used.