Wiring an Additional Ramp Input
18 Digital
Input 7
(Default Ć Ramp1/Ramp2)
Digital input 7 is control function programmable through
parameter P
.007. The following parameters must be set:
P.000:
Control Source
P.001:
Accel T
ime 1 (Ramp 1)
P.002:
Decel T
ime 1 (Ramp 1)
P.006:
Second Menu P
assword
P.007: T
erminal Strip Digital Inputs Configure (Selects
and assigns a control function to digital inputs
6 to 8).
P.008 T
erminal Strip Speed Reference Source (Analog,
Motor Operated P
otentiometer (MOP), or
Preset Speeds)
P.017:
Accel T
ime 2 (Ramp 2)
P.018:
Decel T
ime 2 (Ramp 2)
Note that based on the settings of parameters P
.000, P.007,
P.008, and r
.030 if an RMI board is used, the following
parameters can affect digital input 7.
P.023:
MOP Accel/Decel T
ime
P.024:
MOP Reset Configuration
P.031 to P.038: Preset Speeds 1Ć8
Refer to the GV3000 Programming instruction manual
(D2Ć3339) for additional information.
Terminal 18 On = Ramp 2
Diagram shows factory setting.