Hardware Ref, Installation, and Troubleshooting User guide

7Ć12
Table 7.1 Ć W
iring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description Parameters/Wiring Connections
Wiring a Forward/Reverse Input
19 Digital
Input 6
(Default Ć F
orward/Reverse)
Digital input 6 is control function programmable through
parameter P
.007. The following parameters must be set:
P.000:
Control Source
P.006:
Second Menu P
assword
P.007: T
erminal Strip Digital Inputs Configure (Selects
and assigns a control function to digital inputs 6
to 8).
P.008: T
erminal Strip Speed Reference Source (Analog,
Motor Operated P
otentiometer (MOP), or
Preset Speeds)
P.027:
Reverse Disable
Note that based on the settings of parameters P
.000, P.007,
P.008, and r
.030 if an RMI board is used, the following
parameters can affect digital input 6.
P
.023: MOP Accel/Decel T
ime
P
.024: MOP Reset Configuration
P.031 to P.038: Preset Speeds 1Ć8
Refer to the GV3000 Programming instruction manual
(D2Ć3339) for additional information.
T
erminal 19 On = Reverse Direction
Diagram shows factory setting. F
rom the pulse tachometer
end of the motor
, clockwise rotation indicates forward mo
Ć
tor movement.