Hardware Ref, Installation, and Troubleshooting User guide
7Ć15
Table 7.1 Ć W
iring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description Parameters/Wiring Connections
Wiring the Output Status Relays
28
29
30
31
NormallyĆClosed
Contact
(F
orm B)
Normally
ĆClosed Contact
Common (F
orm B)
Normally
ĆOpen Contact
(F
orm A)
Normally
ĆOpen Contact
Common (F
orm A)
Both Form A and F
orm B contacts are rated for
250 V
AC/30 VDC at 5 amps resistive or 2 amps inductive
load.
The following parameter must be set:
P
.013: Output Relay Configuration
Note that depending on the setting of parameter P
.013, the
relay coil will energize (the normally
Ćopen contact will close
and the normally
Ćclosed contact will open). Refer to the
GV3000 Programming instruction manual (D2Ć3339) for
more information.