User Manual

Technical Specifications
A-3
)
*These are the maximum times from transitioning the input to the drive reacting to the input.
Table A.6 Encoder Feedback Device Specifications (FVC Regulation Only)
Specification Rating
Motor Poles 2, 4, 6, or 8 poles
Overcurrent IET 200% load (based on drive nameplate
rating)
Overload Current Rating 150% for 1 minute (based on drive
nameplate rating)
Speed Control Range 1:600 with 1024 PPR
Speed Control Response 15 Hz (typical)
Encoder Feedback 15 V differential quadrature, encoder
incremental (512 PPR, 1024 PPR, 2048
PPR, 4096 PPR)
Service Factor 1.0
Table A.7 Input Signal Response Times (Maximum)
Signal Type and Source Volts/Hertz Regulation* Vector Regulation*
Keypad START 150 milliseconds 130 milliseconds
Terminal Strip:
START 126 milliseconds 105 milliseconds
STOP, RESET, FL 75 milliseconds 75 milliseconds
Preset Speeds 75 milliseconds 75 milliseconds
Analog Speed/Trim
Reference
16 milliseconds 5 milliseconds
Analog Torque
Reference
N/A 0.5 milliseconds
Network:
START 46 milliseconds + network
transport time
25 milliseconds + network
transport time
STOP, RESET, FL 26 milliseconds + network
transport time
25 milliseconds + network
transport time
Analog Speed/Trim
Reference
5 milliseconds +
network transport time
5 milliseconds +
network transport time
Torque Reference N/A 0.5 milliseconds +network
transport time