User Manual

3-10
GV3000/SE AC Drive Hardware Reference, Version 6.06
*Recommended fuse type: UL Class J, 600 V, time delay, or equivalent.
**The drive contains internal fusing sized to protect the drive. Install fuses to protect the input wiring in
accordance with local codes.
Table 3.12 AC Input Line Fuse Selection Values
Drive
Model Number
Selected Regulation
and
Horsepower Rating
Input Voltage
(+/-10%)
Fuse
Rating*
1V4160 1V4460 V/Hz or Vector (1 HP) 380-460 VAC 6 A
2V4160 2V4460 V/Hz or Vector (2 HP) 380-460 VAC 8 A
3V4160 3V4460 V/Hz or Vector (3 HP) 380-460 VAC 12 A
5V4160 5V4460 V/Hz or Vector (5 HP) 380-460 VAC 20 A
7V4160 7V4260 V/Hz or Vector (7.5 HP) 380-460 VAC 25 A
10V4160 10V4260 V/Hz or Vector (10 HP) 380-460 VAC 35 A
15V4160 15V4260 V/Hz or Vector (15 HP) 380-460 VAC 45 A
20V4160 20V4260 V/Hz or Vector (20 HP) 380-460 VAC 60 A
25G4160 25G4260 V/Hz (25 HP) 380-460 VAC 70 A
25V4160 25V4260 V/Hz or Vector (25 HP) 380-460 VAC 70 A
30V4160 30V4260 V/Hz or Vector (30 HP) 380-460 VAC 100 A
40V4160 40V4260 V/Hz or Vector (40 HP) 380-460 VAC 100 A
50V4160 50V4260 V/Hz or Vector (50 HP) 380-460 VAC 125 A
50R4160 50T4160 Vector (50 HP) or
V/Hz (75 HP)
380-460 VAC 125 A
60G4160 60G4260 V/Hz (60 HP) 380-460 VAC 150 A
75R4160 75T4160 Vector (60-75 HP) or
V/Hz (100 HP)
380-460 VAC 125 A
150 A
125R4160 Vector (100-125 HP) or
V/Hz (125-150 HP)
380-460 VAC 250 A
200V4160 Vector (150-200 HP) or
V/Hz (200 HP)
380-460 VAC **
250V4160 V/Hz or Vector (250 HP) 380-460 VAC **
300V4160 V/Hz or Vector (300 HP) 380-460 VAC **
350V4160 V/Hz or Vector (350 HP) 380-460 VAC **
400V4160 V/Hz or Vector (400 HP) 380-460 VAC **