Module Parameters
B-7
Sets the Reference data that is sent to the drive if any of the
following is true:
Comm Flt Action (18) is set to Send Flt Cfg and communications
are disrupted.
Idle Flt Action (19) is set to Send Flt Cfg and the scanner is put
into Program mode.
Sets the configuration of the Drives that are active in the Multi-Drive
mode. Identifies the connections that would be attempted on a reset
or power cycle.
21 Flt Cfg Ref
Range: 0 to 65535
Default: 0
Type: Read/Write
Reset Required: No
22 MDI I/O Cfg
Range: 0 = Drive 0
1 = Drives 0-1
2 = Drives 0-2
3 = Drives 0-3
4 = Drives 0-4
Default: 0 = Drive 0
Type: Read/Write
Reset Required: Ye s