User guide

B-8
EtherNet/IP Communications Module
Displays the Drives that are active in the Multi-Drive mode.
.
Sets the corresponding node addresses of the daisy-chained drives
when the module Operating Mode Switch (SW1) is set for
Multi-Drive operation.
Important: The settings for these parameters must match the
Comm Node Addr parameter settings in the respective
drives. Each setting must also be unique (no duplicate
node address).
23 MDI I/O Act
Range: 0 = Drive Active
1 = Drive Inactive
Default: xxx0 0000
Type: Read Only
Reset Required: N/A
00000xxx
01234576
0 = Drive 0 Active
1 = Drive 1 Active
2 = Drive 2 Active
3 = Drive 3 Active
4 = Drive 4 Active
5 = Not Used
6 = Not Used
7 = Not Used
24
25
26
27
28
Drv 0 Addr
Drv 1 Addr
Drv 2 Addr
Drv 3 Addr
Drv 4 Addr
Range: 1 - 247
Default: Drv 0 Addr = 100
Drv 1 Addr = 101
Drv 2 Addr = 102
Drv 3 Addr = 103
Drv 4 Addr = 104
Type: Read/Write
Reset Required: Ye s