User guide

7-4
EtherNet/IP Communications Module
7.3 Performing Explicit Messages
Important: There are five basic events in the Explicit Messaging
process defined below. The details of each step will
vary depending on the controller. Refer to the
documentation for your controller.
Retrieve Parameter
Message Response
Complete Parameter
Message
Set up and send
Parameter Message
Format the required data and set up the ladder
logic program to send an Explicit Message
request to the scanner or bridge module
(download).
The scanner or bridge module transmits the
Explicit Message Request to the slave device
over the EtherNet/IP network.
The slave device transmits the Explicit Message
Response back to the scanner. The data is
stored in the scanner buffer.
The controller retrieves the Explicit Message
Response from the scanner’s buffer (upload).
The Explicit Message is complete.
Figure 7.2 – Explicit Message Process