7-16 Application Specific Instructions
TDF Instruction Operation
When the TDF is evaluated with a true rung state, the instruction calculates 
the number of 10 µs ticks that have elapsed from the Start value to the Stop 
value and places the result into the Destination location. The TDF instruction 
with float addresses accurately computes the time difference between the Start 
and Stop timestamps captured within 10.48575 seconds of each other 
(1048575 10 µs ticks). The TDF with float addresses calculates an invalid result 
if more than 10.48575 seconds have elapsed between the Start and Stop 
timestamps. The TDF with integer addresses accurately computes the time 
difference between the Start and Stop timestamps captured within 655.36 ms 
of each other (65536 10 µs ticks). The TDF with integer address calculates an 
invalid result if more than 655.36 ms have elapsed between the Start and Stop 
timestamps. It is up to you to assure that the timestamps are captured within 
the valid time difference range.
TIP
Measurements were calculated with both 
communication channels active and no devices 
connected to the processor. Worst case accuracy is 
improved by shutting down an unused 
communication channel.