8-4 Block Transfer Instructions
Figure 8.1 Successful Block Transfer
Successful Block Transfer Read/Write
Figure 8.1 illustrates a successful BT operation.
1. The SLC control program copies new data to the data file (BTW only) 
and solves the BT rung true, which sets the enable (EN) bit.
2. The scanner detects that the EN bit is set, validates the control block 
information, puts the BT request on the RIO link successfully, and since 
no other BTs are pending for the same logical rack, sets the enable 
waiting (EW) and start (ST) bits.
3. The scanner receives a BT reply (with no errors) from the RIO link 
device, copies the received data to the data file (BTR only) and sets the 
done (DN) bit.
4. The SLC control program detects the DN bit, processes the BTR data 
and solves the BT rung false, which clears the enable (EN) bit.
5. The scanner detects that the SLC control program has completed 
processing (because the EN bit is clear) and clears the EW, ST and DN 
bits. At this point, the SLC control program could re-initiate the same 
BT operation by solving the BT rung true again.
Control Bits
Status Bits
EN
TO
EW
ST
ER
DN
122435
Control Information
Status Information