9-24 Proportional Integral Derivative Instruction
Using the SCL Instruction
Use the following values in an SCL instruction to scale common analog input
ranges to PID process variables
Use the following values in an SCL instruction to scale control variables to
common analog outputs.
Using the SCP Instruction
Use the following values in an SCP instruction to scale your analog inputs to
the PV range and scale the CV range to your analog output
Table 9.37 SLC Instruction
Parameter 4 to 20mA 0 to 5V 0 to 10V
Rate/10,000 12,499 10,000 5,000
Offset -4096 0 0
Table 9.38 SLC Instruction
Parameter 4 to 20mA 0 to 5V 0 to 10V
Rate/10,000 15,239 10,000 19,999
Offset 6242 0 0
Table 9.39 SCP Instruction
Parameter 4 to 20mA 0 to 5V 0 to 10V
Input minimum 3277 0 0
Input maximum 16384 16384 32767
Scaled minimum 0 0 0
Scaled maximum 16383 16383 16383