Installation manual
Publication 1747-RM001G-EN-P - November 2008
10-14 ASCII Instructions
Example
The following shows the channel status as 001F.
Example
The Error bit (ER) is set during the execution of the instruction if:
• the instruction is aborted due to channel mode change.
• the Unload bit (UL) is set and the instruction is not executed.
Integer to String (AIC)
The AIC instruction converts an integer value (-32,768 and 32,767) to an
ASCII string. The source can be a constant or an integer address.
Example
Table 10.7 Control Block Structure
Channel
Status
Bit
1514131211109876543210
Bit Reserved DTR DCD DSR RTS CTS
Line 0000000000011111
Channel
Status
001F
AIC
Integer to String
Source N7:98
0<
Dest ST10:6
AIC
Output Instruction
Fixed SLC
5/01
SLC
5/02
SLC
5/03
SLC
5/04
SLC
5/05
•••