SLC Communication Instructions 12-11
MSG Instruction Configuration Options
The following configuration options are available on all SLC 5/02 and higher 
processors. 
• Peer-to-peer Read/Write on a local network to another SLC 500 
processor
• Peer-to-peer Read/Write on a local network to a 485CIF device (PLC-2 
emulation)
In addition, the following configuration options are available on all 
SLC 5/03 and higher processors.
• Peer-to-peer Read/Write on a local network to a PLC-5 processor 
• Peer-to-peer Read/Write on a remote network to another SLC 500 
processor
• Peer-to-peer Read/Write on a remote network to a 485CIF device 
(PLC-2 emulation)
• Peer-to-peer Read/Write on a remote network to a PLC-5 processor 
• Peer-to-peer Read/Write on a local network to Modbus slave devices
In addition, the following configuration option is available on SLC 5/05 
processors.
• Peer-to-peer Read/Write Multihop from Ethernet to a Logix processor 
(ControlLogix, FlexLogix, and CompactLogix), or other EtherNet/IP 
device, or through ControlLogix gateway to ControlNet, DH+, or 
DH-485.
MSG Instruction Parameters
Enter the following parameters when programming this instruction.
• Read/Write - Read indicates the local processor (processor in which 
the instruction is located) is receiving data; write indicates the local 
processor is sending data.
• Target Device identifies the type of device which responds to the MSG 
command. Valid options are:
– 500CPU, if the target device is another SLC processor
– 485CIF, if the target device is a PLC-2 emulator device
– PLC-5, if the target device accepts PLC-5 commands
(1)
– Modbus, if the target device is configured as Modbus RTU Slave
(1)
SLC 5/03 and higher only.