12-34 SLC Communication Instructions
Table 12.14 SLC 5/05 Channel 1 Read or Write, Local or Remote to an SLC 500 CPU or PLC-5 (without Logical ASCII/Symbolic
Addressing)
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word 0 EN ST DN ER CO EW NR TO Error Codes
Word 1 Reserved Remote Station Address (Remote only)
Word 2 Number of Elements
Word 3 File Number
Word 4 File Type (based on local source or destination address)
Word 5 Element Number
Word 6 Not Used
Word 7 Remote Bridge Address (Remote Only) Reserved (Internal Messaging Bits) WQ
Word 8 Reserved (Internal Messaging Bits) Message Timer Preset
Word 9 Message Timer Scaled Zero
Word 10 Message Timer Accumulator
Word 11 Reserved (Internal Messaging Bits)
Word 12 AO=
0
Reserved (Internal Messaging Bits)
Word 13 Reserved (Internal Messaging Bits)
Word 14
First Byte of IP Address String
(1)
Second Byte of IP Address String
Word 15 Third Byte of IP Address String ...
... ... ...
... ... ...
Word 34 Forty-First Byte of IP Address String NULL Byte of Longest IP Address String
Word
35
(3)
Not Used
Ethernet Message Type = 0
(2)
, 10h
(3)
, or 11h
(3)
Word
36
(3)
ASA Service Internal Object Identifier (IOI) Size in Words (1 to 5)
Words
37 - 41
(3)
ASA Internal Object Identifier (IOI)
Word
42
(3)
Not Used Connection Path Size in Words (1 to 8)
Words
43 - 50
(3)
Connection Path
(1)
The IP Address format is up to 42 ASCII characters including a terminating NULL character. The first byte in the array is the left most character in the string as written. For
example: If the IP Address is 423.156.78.012, the first byte is the ASCII character “4”. If the MSG destination is an INTERCHANGE client on a host computer, the destination
is specified as “client” and stored as a NULL terminated string.
(2)
Not MultiHop MSG.
(3)
MultiHop MSG.