SLC Communication Instructions 12-47
Parameters for Target Device on the General Tab
• Message Timeout(x1 ms)
The amount of time in milliseconds that the scanner will wait for a reply
to the explicit message command. Range is 2 to 32767.
• ControlNet Addr (dec)
The target ControlNet node address. Valid range is 1 to 99. If you enter
in the local scanner’s ControlNet node address, the command is
executed by the local scanner.
• Service
This dropdown allows you to select services based on name rather than
Service Code. The Custom service allows you to enter in any Service
Code in the hexadecimal range of 1 to 7F. The services listed in the
dropdown selection are:
– Read Assembly.
– Write Assembly.
– Write Output Point.
– Read Output Point.
– Read Input Point.
– Read Parameter.
– Write Parameter.
– Read Analog Input.
– Write Analog Output.
– Generic Get Attribute Single.
– Generic Set Attribute Single.
– Generic Get Member.
– Generic Set Member.
– Reset Identity Object.
– Custom.
• Service Code (hex)
This field is read-only unless the Custom Service is selected. Possible
Service Codes are 1 to 7F (hex). See Volume 1 of the CIP Common
Specification, Appendix A, for the list of valid explicit messaging Service
Codes.