SLC Communication Instructions 12-53
Parameters for Target Device on the General Tab
Message Timeout(x1 sec)
The amount of time in seconds that the processor will wait for a reply
from the scanner to the explicit message command. Range is 0, 2 to 255.
Like the Message Timeout in a standard MSG instruction, a value of 0
disables the Message Timeout and a value of 1 second gets bumped to 2
seconds upon instruction execution. If the built-in Message Timeout is
disabled, user programmed timeout logic must be included to avoid a
message lockup in the case where a reply is lost.
DeviceNet Addr (dec)
The target DeviceNet node address. Valid range is 0 to 63. If you enter
in the local scanner’s DeviceNet node address, the command is
executed by the local scanner.
Service
This pulldown lets you select services based on name rather than Service
Code. The Custom service allows you to enter in any Service Code in
the hexadecimal range of 1 to 7F. The services listed in the pulldown
selection are:
Read Assembly.
Write Assembly.
Write Output Point.
Read Output Point.
Read Input Point.
Read Parameter.
Write Parameter.
Read Analog Input.
Write Analog Output.
Generic Get Attribute Single.
Generic Set Attribute Single.
Reset Identity Object.
Custom.
Service Code (hex)
This field is read-only unless the Custom Service is selected. Possible
Service Codes are 1 to 7F (hex). See Volume 1 of the CIP Common
Specification, Appendix A, for the list of valid explicit messaging Service
Codes.