1-8 Processor Files
Control Data File (R6:)
These instructions use various control bits. These are 3-word elements, used
with bit shift, FIFO, LIFO, sequencer instructions, and ASCII instructions
ABL, ACB, AHL, ARD, ARL, AWA, and AWT. Word 0 is the status word,
word 1 indicates the length of stored data, and word 2 indicates position. This
is shown in Table 1.10.
In the control element, there are eight status bits and an error code byte. A
fixed controller and an SLC 5/01 control element has six bits. Bits EU and
EM are not used by the processor.
C5:0/11 or C5:0/UN Underflow bit
C5:0/10 or C5:0/UA Update accum. bit (use with HSC in fixed controller only)
C5:0.1 or C5:0.PRE Preset value of the counter
C5:0.2 or C5:0.ACC Accumulated value of the counter
C5:0.1/0 or
C5:0.PRE/0
Bit 0 of the preset value
C5:0.2/0 or
C5:0.ACC/0
Bit 0 of the accumulated value
Table 1.9 Counter File Addressing Format
Explanation
Table 1.10 Three Word Element Structure
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 Word
EN
EU
(1)
DN
EM
(1)
ER UL IN FD Error Code 0
Length of Bit Array or File (LEN) 1
Bit Pointer or Position (POS) 2
(1)
Not used in Fixed or SLC 5/01.
Table 1.11 Control Elements
Addressable Bits Addressable Words
EN = Enable LEN = Length
EU = Update Enable POS = Position