Installation manual
Publication 1747-RM001G-EN-P - November 2008
SLC Communication Instructions 12-59
• Data Table Address (Send Data)
If Size in Words (Send Data) is non-zero, then this field requires a
starting integer (N) file address for storing the Send Data.
• Data Table Address (Receive Data)
If Size in Words (Receive Data) is non-zero, then this field requires a
starting integer (N) file address for storing the Receive Data.
Parameters for Target Device on the General Tab
• Message Timeout (x1 sec)
Message Timeout for the EEM cannot be modified in the Setup Screen.
It is assigned by the processor and is determined by adding the Channel
1 Msg Connection Timeout value to the Channel 1 Msg Reply Timeout
value, then adding five seconds. This value can be modified by changing
one or both of the timeout values in the Channel 1 Channel
Configuration Screen. The modified message timeout applies to all
EEM and Ethernet MSG instructions.
• MultiHop
Always Yes.
• Service
This pulldown lets you select services based on name rather than Service
Code. The Custom service lets you enter in any Service Code in the
hexadecimal range of 1 to 7F. The services listed in the pulldown
selection are:
– Read Assembly.
– Write Assembly.
– Write Output Point.
– Read Output Point.
– Read Input Point.
– Read Parameter.
– Write Parameter.
– Read Analog Input.
– Write Analog Output.
– Generic Get Attribute Single.
– Generic Set Attribute Single.
– Reset Identity Object.
– Custom.