Installation manual

Publication 1747-RM001G-EN-P - November 2008
13-100 SLC Communication Channels
Table 13.31 Define these communication parameters when configuring an SLC 5/03, SLC 5/04, or SLC 5/05 processor for ASCII
communication.
Tab Parameter Default Selections
Channel 0 User Baud Rate 19200 Toggles between the communication rate of 110, 300, 600, 1.2K, 2.4K, 4.8K,
9.6K and 19.2K (additional rate of 38.4K for SLC 5/04 and SLC 5/05 only).
Parity None Toggles between None, Odd, and Even.
Stop Bits 1 Toggles between 1, 1.5, and 2.
Data Bits 8 Toggles between 7 and 8.
Delete Mode Ignore Toggles between Ignore, CRT, and printer. This parameter is dependent on the
Echo parameter being Enabled.
Echo Disabled Toggles between Disabled and Enabled.
RTS Off Delay 0 Allows you to select the RTS off delay value in increments of 20 ms. Valid
range is 0 to 65535 (in 20 ms increment). Only valid for Half-duplex Control Line
settings.
RTS Send Delay 0 Allows you to select the RTS send delay value in increments of 20 ms. Valid
range is 0 to 65535 (in 20 ms increment). Only valid for Half-duplex Control Line
settings.
Control Line No Handshaking Toggles between No Handshaking, Half-duplex With Continuous Carrier,
Half-duplex Without Continuous Carrier, and Full-duplex Modem.
XON/XOFF Disabled Toggles between Disabled and Enabled.
Termination 1
Termination 2
\d
\ff
Specify \ff for no termination character.
Append 1
Append 2
\d
\a
Specify \ff for no append character.