SLC Passthru Communications 14-13
SLC 5/05 Passthru Error Codes
A SLC 5/05 passthru processor may respond to a MSG instruction or RSLinx
with an error code of 20H under the following conditions.
The routing table integer file number is out of range (9 to 255).
The routing table file does not exist in the user program directory or is
less than 2 word elements in length.
The IP address entry in the routing table does not exist.
Lack of available connections.
Optimizing RSLinx Channel 1 to DF1 Half-duplex Master/DF1
Radio Modem Passthru
Use the following procedure to get RSWho to browse from channel 1 through
the SLC 5/03, 5/04, and 5/05 processors when either the DF1 Half-duplex
Master or DF1 Radio Modem channel 0 driver is configured.
1. If using a SLC 5/05 as the passthru processor, be sure to configure the
IP address of the PC running RSLinx/RSWho into the SLC 5/05
Passthru Routing Table.
2. Make sure that the DF1 passthru enable bit (S:34/5) is set in the
passthru processor.
3. Configure the appropriate RSLinx driver to communicate via DH-485
with an SLC 5/03 passthru processor, via DH+ with an SLC 5/04
passthru processor or via Ethernet with an SLC 5/05 passthru
processor.
TIP
RSLinx must be directly connected on the same
network (DH-485, DH+, or Ethernet) as the
passthru processor for passthru to work.