Publication 1747-RM001G-EN-P - November 2008
Messaging Examples 15-21
The Passthru Routing Table File is the integer file used by the processor to
store routing table IP addresses and link them to unique node addresses.
Passthru Routing Table
The passthru routing table is located under the channel configuration selection
in RSLogix 500 Programming Software. If a Passthru Routing Table File
number was entered in the Chan. 1 - System tab in the Channel Configuration
dialog box, click on the + in front of Channel Configuration to reveal the
routing table selection.
For the Step by Step procedure for this example refer to Knowledgebase
Document Number: G20027.
IMPORTANT
Channel 0 Source ID must be set to 0 when SLC 5/05
(IP Address 100.100.115.9) is used as the bridge
between DF1 full-duplex and Ethernet.
IMPORTANT
The routing table must contain the IP address of SLC
5/05 (IP Address 100.100.115.1) at station target node
one, as shown in the routing table above. Target
node one was identified as the target node in the SLC
5/03 Message Setup dialog box.