Installation manual
Publication 1747-RM001G-EN-P - November 2008
Troubleshooting Faults  16-11
I/O Errors
ERROR CODES: The characters xx in the following codes represent the slot 
number, in hexadecimal. If the exact slot cannot be determined, the characters 
xx become 03 for fixed controllers and 1F for modular controllers. Refer to 
the table below.
RECOVERABLE I/O FAULTS (SLC 5/02 and higher processors only): 
Many I/O faults are recoverable. To recover, you must disable the specified 
slot, xx, in the user fault routine. If you do not disable slot xx, the processor 
will fault at the end of the scan.
Table 16.5 Slot Numbers
Slot xx
(1)
(1)
Slot numbers (xx) in hexadecimal.
Slot xx Slot xx Slot xx
0
1
2
**3
4
5
6
7
00
01
02
03
04
05
06
07
8
9
10
11
12
13
14
15
08
09
0A
0B
0C
0D
0E
0F
16
17
18
19
20
21
22
23
10
11
12
13
14
15
16
17
24
25
26
27
28
29
30
*
18
19
1A
1B
1C
1D
1E
1F
TIP
An I/O card that is severly damaged may cause the 
processor to indicate that an error exists in slot 1.