Troubleshooting Faults 16-13
xx56 The chassis configuration specified
in the user program is detected as
being incorrect.
The chassis configuration specified by
the user does not match the hardware.
Correct the chassis configuration,
reload the program and run.
xx57 A specialty I/O module has not
responded to a Lock Shared
Memory command within the
required time limit.
The specialty I/O module is not
responding to the processor in the
time allowed.
Cycle chassis power. If this does not
correct the problem, refer to the user
manual for the specialty I/O module.
You may have to replace the module.
xx58 A specialty I/O module has
generated a generic fault. The card
fault bit is set (1) in the module’s
status byte.
Refer to the user manual of the
specialty I/O module.
Cycle chassis power. If this does not
correct the problem, refer to the user
manual for the specialty I/O module.
You may have to replace the module.
xx59 A specialty I/O module has not
responded to a command as being
completed within the required time
limit.
A specialty I/O module did not
complete a command from the
processor in the time allowed.
Refer to the user manual for the
specialty I/O module. You may have to
replace the module.
xx5A Hardware interrupt problem. If this is a discrete I/O module, this is
a noise problem. If this is a specialty
I/O module, refer to the user manual
for the module.
Cycle chassis power. Check for a
noise problem and be sure proper
grounding practices are used. If this is
a specialty I/O module, refer to the
user manual for the module. You may
have to replace the module.
xx5B G file configuration error - user
program G file size exceeds the
capacity of the module.
G file is incorrect for the module in
this slot.
Refer to the user manual for the
specialty I/O module. Reconfigure the
G file as directed in the manual, then
reload and run.
xx5C M0-M1 file configuration error -
user program M0-M1 file size
exceeds capacity of the module.
M0-M1 files are incorrect for the
module in this slot.
Refer to the user manual for the
specialty I/O module. Reconfigure the
M0-M1 files as directed in the
manual, then reload and run.
xx5D Interrupt service requested is not
supported by the processor.
The specialty I/O module has
requested service and the processor
does not support it.
Refer to the user manual for the
specialty I/O module to determine
which processors support use of the
module. Change processor to one that
supports the module.
xx5E Processor I/O driver (software)
error.
Corrupt processor I/O driver software. Reload program using RSLogix
software.
xx60
through
xx6F
Identifies an I/O module specific
recoverable major error.
--
xx70
through
xx7F
Identifies an I/O module specific
non-recoverable major error.
--
xx80
through
xx8F
Identifies a specialty I/O module
specific non-recoverable major
error.
--
Table 16.6 I/O Errors (Continued)
Error Code
(Hex)
Description Probable Cause Recommended Action