SLC 5/03 (OS30x), SLC 5/04 (OS40x) and SLC 5/05 (OS50x) Firmware History A-17
Using RSLogix 500 V6.30 and higher, you can disable the SLC 5/05
SNMP functionality from within the Channel 1 Configuration by
unchecking the SNMP Server Enable check box shown in Figure A.1.
The default (checked SNMP Server Enable box shown in Figure A.1)
allows you to connect to the SLC 5/05 using an SNMP client. Although
this parameter can be downloaded to the processor as part of a program
download or changed and applied while online with the processor, a
processor power cycle is required in order for the change to take affect.
Selectively Disabling Individual Data Files from Web View
Using RSLogix 500 V6.30 and higher, you can disable individual data
files from being viewed via any web browser by selecting the data file’s
properties page and checking the Web View Disable check box as
shown in Figure A.2. Any data file property changes must be made
offline and downloaded to the processor.
Figure A.2 Web View Disable Check Box
More Secure Processor Ownership Behavior
Several RSLogix 500 online operations require obtaining the processor
Edit Resource/Processor Ownership in order to ensure that one
programming terminal has exclusive capability of performing any of
these operations at a time. These operations include downloading,
online editing, and applying channel configuration changes. An
enhancement was made in FRN 9 to ensure this ownership exclusivity
via EtherNet/IP, even when multiple programming terminals are
routing through a single ControlLogix gateway. With FRN 9, if routing
through a ControlLogix gateway or connecting to the same Ethernet
IMPORTANT
Since SNMP is used as part of the ControlFlash firmware
upgrade process, the SNMP server must be enabled prior
to beginning the firmware upgrade.
Web View Disable