Installation manual

Publication 1747-RM001G-EN-P - November 2008
B-10 SLC Status File
S:1/12 Static Config
(See table on
page B-60 for all
setting
combinations.)
Load Memory Module and Run Bit
With this bit, you can overwrite a processor program with a
memory module program by cycling processor power. A
programming device is not required. The processor will
attempt to enter the REM Run mode, regardless of what mode
was in effect before cycling power:
••••
••••
•••
Table B.2 Status File Functions (Continued)
Address Classification Description Fixed
5/01
5/02 5/03 5/04 5/05
Mode before Powerdown Mode after Powerup
REM Test/Rem Program
REM Run/Rem Fault
REM Idle/Rem Download
REM Run
REM Run
REM Run
Mode before Powerdown Mode after Powerup
(same keyswitch position)
Run
Idle
Program/Download
Fault after Run
Fault after Program
RUN
Run
PROGram
RUN
PROGram