Installation manual

Publication 1747-RM001G-EN-P - November 2008
SLC Status File B-27
Table B.3 S:6 Error Codes
Address Error
Code
(Hex)
Errors Fault Classification Processor
Non-
User
User Fixed
5/01
5/02 5/03 5/04 5/05
Non-
Recov
Recov
S:6
continued
0001 NVRAM error. X ••••
0002 Unexpected hardware watchdog
timeout.
X ••••
0003 Memory module memory error. This
error can also occur while going into
the REM Run mode.
X•
0004 Memory error occurred while in the Run
mode.
X•
0005 Reserved X•
0006 Reserved X•
0007 Failure during memory module transfer. X•
0008 Internal software error. X•
0009 Internal hardware error. X•
0010 The Processor does not meet the
required revision level.
X ••••
0011 The executable program file number 2
is absent.
X ••••
0012 The ladder program has a memory error. X ••••
0013 The required memory module is
absent or
S:1/10 or S:1/11 is not set as
required by the program.
X ••••
0014 Internal file error. X ••••
0015 Configuration file error. X ••••
0016 Startup protection after power loss.
Error condition exists at powerup when
bit S:1/9 is set and powerdown
occurred while running.
X•
0017 NVRAM/memory module user program
mismatch.
X•
0018 Incompatible user program - Operating
system type mismatch. This error can
also occur during powerup.
X•
0019 Missing or duplicate label was
detected.
X•
001F A program integrity problem occurred
during an online editing session.