Installation manual

Publication 1747-RM001G-EN-P - November 2008
D-10 Programming Instruction References
HSC
(5)
High-speed Counter (SLC
5/01)
counter none
preset 1 to 32,767
counter direct C none
preset -32,768 to 32,767
accum -32,768 to 32,767
source direct B and N none
length always 5
IID
(6)
I/O Interrupt Disable slots double hex word
(list of slots)
IIE
(6)
I/O Interrupt Enable slots double hex word
(list of slots)
IIM Immediate Input with
Mask
slot direct I none
mask direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R, N,
A, ST, M
-32,768 to 32,767
length
(SLC 5/03, 5/04,
and 5/05)
1 to 32
INT
(3)
I/O Interrupt none
IOM Immediate Output with
Mask
slot direct O none
mask direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R, N,
A, ST, M
-32,768 to 32,767
length
(SLC 5/03, 5/04,
and 5/05)
1 to 32
JMP Jump label number 0 to 999
JSR Jump to Subroutine subroutine file
number
3 to 255
LBL Label Declaration label number 0 to 999
LEQ Less Than or Equal To source A direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R, N,
F, A, ST, M
none
source B direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R, N,
F, A, ST, M
-32,768 to 32,767
f-min to f-max
LES Less Than source A direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R, N,
F, A, ST, M
none
source B direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R, N,
F, A, ST, M
-32,768 to 32,767
f-min to f-max
Table D.3 Available Addressing Modes (Continued)
Instruction Description Instruction
Parameter
Valid Addressing
Mode(s)
Valid File Types Immediate
Values