Specifications
Publication 1747-SG001E-EN-E - February 2013
6 System Overview
Vibration, operating IEC 60068-2-6 (Test Fc, Operating):
1 g @ 5…2000 Hz
Vibration, nonoperating 2.5 g @ 5…2000 Hz
Shock, operating 30 g (3 pulses, 11 ms) – for all modules except relay contact
10 g (3 pulses, 11 ms) – for relay contact modules 1746-OWx and
1746-IOx combo
Shock, nonoperating 50 g, 3 pulses, 11 ms
Free fall (drop test) Portable, 2.268 kg (5 lb) or less @ 0.762 m (30 in.), six drops
Portable, 2.268 kg (5 lb) or less @ 0.1016 m (4 in.), three flat drops
Isolation voltage Isolation between communication circuits: 500V DC
Isolation between backplane and I/O: 1500V AC
Certifications
Certifications when
product is marked
(1)
(1) See the Product Certification link at http://www.rockwellautomation.com/products/certification/ for
Declarations of Conformity, Certificates, and other certification details.
Value
UL UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations. See
UL File E10314.
c-UL UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for Canada. See UL File E10314.
CE European Union 2004/108/EC EMC Directive, compliant with:
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
KC Korean Registration of Broadcasting and Communications Equipment,
compliant with:
Article 58-2 of Radio Waves Act, Clause 3
Environmental Specifications
Attribute Value