CHAPTER4
OperationalTest
LEDpanel(Standard)
StartUpinNormalACMode
NOTE:ChargetheUPSformorethaneight(8)hoursafterunpackingtoensureitisfullycharged
beforeuse.
1. Beforecommencingtheinstallation,pleaseensuretheUPSisproperlygrounded.
2. EnsurethattheutilityvoltagematchestheinputvoltageoftheUPS.
3. ConnectUPSmainpowercordtotheACutilitypoweroutlet.
4. TurnONtheACpowersource.AlloftheLEDsonthefrontpaneldisplaywillflashonce
afterthree(3)seconds,except 、 whichwillremainilluminated(Green).Atthe
sametime,thefanattherearoftheUPSwillstartoperating.
5. Pressthe‘ ’switchforapproximatelythree(3)secondstostarttheUPS.Thebuzzer
willbeepandthe and , LEDswilllightupafter30seconds.Thestart‐up
procedureiscompletedandtheUPSoutletsareavailable..
6. ItisadvisabletoperformaBatteryModeTestbeforeconnectingtheloadstotheUPSto
ensurethebatteriesareworkingproperly.
7. SwitchOFFtheACpowersourceaftertheUPShadbeenswitchedON.The LEDonthe
frontpaneldisplaywillturnOFFwhilethe LEDwillbeilluminated.Thebuzzeralarm
willbeepintermediately,indicatingtheUPSisinBatteryMode.Connectanon‐critical
loadtotheUPSoutletstoconfirmpowerfromthebattery.Repeatthetestbyswitching
ONandOFFtheACpowersourcetoensuretheUPSisfunctioningproperly.
Start‐upinBatteryMode(ColdStart)
ThisUPScanbeswitchedONforoperationwithoutthepresenceofanACpowersource.
Pressandholdthe‘
’switchuntilthebuzzerbeeps,thenreleasetheswitch.Withinthe
next10seconds,pressandholdthe‘ ’switcha2
nd
time.TheUPSshallperformitsstart‐up
procedure.The and 、 LEDswilllightupafter30secondsandthebuzzerwillbeep
intermediatelytoindicatesuccessfulpowerON.