Specifications
38 ROCPOWER ‐ ROCWAVEusermanual
CommunicationPortExplanation
TheUPSisequippedwithEPOdrycontactsinput,trueRS232&USBCommunicationportsas
standard.ThisprovidescommunicationwithbundledUPSmonitoringsoftwareforremote
monitoringofUPSstatusviaPC.
Therearefour(4)otheroptionalinterfacecardsavailabletomeetvariouscommunication
needs,i.e.,DCE(drycontactrelaycard),R2E,USEandSNMP/WEBcard(seeChapter8).
TheUPSbundledsoftwareiscompatiblewithmanyoperatingsystemssuchasWindows98,
2000,ME,NT,XPandVista.ForotherapplicationssuchasNovell,NetWare,UNIX,Linux,please
contactyourlocaldealerforsuitablesoftware.
Allthecommunicationports(includingoptionalcards)canbeactiveandusedsimultaneouslyto
monitortheUPSstatus.However,thecommunicationinterfacewiththehighestpriorityhas
theabilitytocommandandcontroltheUPS.Thepriorityofthesecommunicationinterfacesare
asfollows:
HighestPriority(indescendingorder),
1)
EPOinputport
2) OptionalInterfacecard
3) USB
4) RS232
TrueRS232PortDescriptions
TheRS232interfacehasbeensetasfollows:
BaudRate 2400bps
DataLength 8bits
StopBit 1bit
Parity None