OverloadCondition
TheworkingprincipleoftheUPSwhenoverloadedisillustratedasfollows:

Fig4
1.Generally,moderndayelectronicsandITequipmentgenerateaninrushcurrentwhen
switchingon.Theamountofinrushcurrentvariesfromequipmenttoequipment.Somecan
beashighassix(6)timesitsratedcapacitywhileothersproducenegligibleinrush.To
preventseveredamagetoitsinvertercausedbytheinrushproducedbytheloads,theUPSis
equippedwithelectronicsoverloadprotectionfeatureasstandard.IftheUPSloadingis
>105~120%ofitscapacity,itwillswi tchtoBypassModein30seconds toprotecttheinverter.
Iftheoverloadconditioniseliminatedbyreducingtheloadto<105%,theUPSwill
automaticallyswitchbacktoInverterMode.IftheUPSloadingis>150%ofitscapacity,the
inverterwillimmediatelyshutdown.