Specifications
50 ROCPOWER ‐ ROCWAVEusermanual
CHAPTER9
Troubleshooting
WhentheUPSbecomesfaultyormalfunctionsduringoperation,youmaycheckthefaultlists
belowforpossiblesolutions.Should theproblempersist,pleasecontactyourlocaldealerfor
assistance.
Situation
CheckItems/LED
Display
Solution
UPSFault LED
Readtheerrorcode
(seenextpagefor
errorreadings)
displayedbythe
variousLEDsand
verifythefaultas
follow:
1.Er05,Er25,
2.Overload
3.Er11(UPSOverheating)
4.Sitewiring/Ground
fault
5.Er14(Fansoutoforder)
6.Othererrorcodes
1. Checkbatteryconnections.Measure
Batteryvoltagetoensurebatteriesare
charged.Rechargebatteriesfor8hoursif
necessary.Simulateutilityoutagetoverify
thattheUPSisabletoprovideDCback‐
up.Otherwiseconsultyourlocaldealer.
2.Disconnectsomenon‐criticalloadsfrom
theUPSoutputuntiltheoverloadceases.
Checkifthereisanyshortcircuit
betweencablessuchasbroken
insulation.Replacethecablesif
necessary.
3.Removeanyobjectsobstructingthe
ventilationlouvers.Verifythatthe
coolingfansareworkingproperly.
Contactyourlocaldealertoreplacethe
fansifnecessary.
4.Verifythatthe“Live(hot)”OK“Neutral”
wiresoftheutilityAChavebeen
attachedcorrectly.DoesGround‐Neutral
Voltageexceedacceptablelimit?
5.Verifythattheventilatingfansare
functioningproperly.Donotattemptto
replacethefansbyyourself.Contact
yourlocaldealerforreplacement.
6.Consultyourlocaldealerforassistance.