SYSTem:FIRMware:UPDate <Directory>
This command starts a firmware update using the *.msi files in the selected directory.
The default path is D:\FW_UPDATE. The path is changed via the MMEMory:COMMent
command. To store the update files the MMEMory:DATA command is used.
Only user accounts with administrator rights can perform a firmware update.
Setting parameters:
<Directory>
Example:
SYST:FIRM:UPD 'D:\FW_UPDATE'
Starts the firmware update from directory "D:\FW_UPDATE".
SYSTem:FORMat:IDENt
<IDNFormat>
This command selects the response format to the *IDN? query.
Parameters:
<IDNFormat> NEW | FSL
R&S FPL1000 format
Format is also compatible to the R&S FSL and R&S FSV family
*RST: not reset!
11.10.8 Using Service Functions
DIAGnostic:SERVice:SFUNction......................................................................................975
DIAGnostic:SERVice:SFUNction:LASTresult?...................................................................976
DIAGnostic:SERVice:SFUNction:RESults:DELete............................................................. 976
DIAGnostic:SERVice:SFUNction:RESults:SAVE................................................................976
DIAGnostic:SERVice:SINFo?.......................................................................................... 976
SYSTem:PASSword[:CENable]........................................................................................977
SYSTem:PASSword:RESet............................................................................................. 977
DIAGnostic:SERVice:SFUNction <ServiceFunction>
This command starts a service function.
The service functions are available after you have entered the level 1 or level 2 system
password.
Parameters:
<ServiceFunction> String containing the ID of the service function.
The ID of the service function is made up out of five numbers,
separated by a point.
• function group number
• board number
• function number
• parameter 1 (see the Service Manual)
• parameter 2 (see the Service Manual)