User Manual

FIGURE 7:
Electrolyte level
6mm - 13mm
1/4" - 1/2"
Electrolyte level should
be kept below vent
tube to prevent overflow
during charge.
16
CAUTION: Do not add water or electrolyte to cells before initial charging unless plates are
e
xposed. If so, add distilled water until plates are submerged. Please contact Rolls Technical
Support if you have any questions or concerns.
NOTE: If the battery cells require watering more than once every two (2) months the
programmed charging voltages may be too high. Adjust and monitor accordingly. If a particular
cell requires significantly more water than others this may be a sign of charge imbalance in the
battery bank caused by resistance and/or cell failure. Typically, Series 4000 & 4500 models will
require watering every 30-60 days. Series 5000 batteries generally require watering every
60-90 days as these models are designed with a higher electrolyte reserve allowing longer
watering intervals. Frequency may vary considerably due to operating temperature, depth of
discharge, cycle frequency and humidity.
BATTERY MAINTENANCE & STORAGE
Batteries should be kept clean at all times. If installed or stored in a dirty location, regular
cleaning should be performed. Before doing so, assure that all the vent caps are tightly
fastened. Using a solution of water and baking soda (100g per litre), gently wipe the battery
and terminals with a damp sponge, then rinse with water and wipe dry.
A common cause of failure with Flooded battery banks is poor maintenance. Systems are
often professionally installed and maintenance left to homeowners who are unaware of
the requirements or simply choose not to complete the proper maintenance procedures. To
maintain cycle life and protect your investment, Flooded batteries should be checked regularly
and topped up with distilled water as needed. Customers will often neglect this for extended
periods of time, and when doing so, over-water the cells resulting in loss of electrolyte,
overflow during charging and/or corrosion issues. Failing to top up cells may result in plate
exposure, overheating and possible explosion.
ELECTROLYTE - ADDING DISTILLED WATER
Only distilled (preferred), deionized or reverse osmosis water should be used in Flooded
battery cells. Improper watering may cause internal cell damage. Test water to confirm
a PH reading of 7 or less and no Total Dissolved Solids (TDS < 5 PPM).
NOTE: Do not add sulfuric acid to Flooded battery cells during normal top up. In the case
of accidental spill, premixed electrolyte (1.265 S.G.) may be used to refill cells.