VRLA AGM ABSORPTION CHARGE TIME
Where : T = 0.38 x C /I
T = ABSORPTION CHARGE TIME
C = 20 hr RATED CAPACITY (total battery bank)
I = Charging Current (Amps) (recommended 20% of C/20 discharge rate)
0.38 = ( 20%/50%) + 5% (5% is added due to losses)
EXAMPLE:
2 strings of 6 Volt S6-460AGM models
20 hr AH rate = 415 AH x (2 strings) = 830 AH
I = 20% of 830 AH = 166 Amps
T = 0.38 x 830/166 = 1.9 hrs
VRLA AGM FLOAT STAGE AND TERMINATION
To maintain 100% SOC, the charger continues output to the battery bank at the
programmed Float voltage and End Amps current indefinitely or until the charger
is shut off or unplugged. The profile in Table 5: VRLA AGM Charge Voltage may
be used with or without the Float stage. Without the Float stage, recharge may be
terminated based on time. This will vary by depth of discharge and charge current,
or percentage recharge (105-110%).
ROLLS VRLA AGM BATTERY CHARGE
VOLTAGE PARAMETERS
NOTE: Use the highlighted voltage set points when charge equipment is supplied
with a temperature sensor. Set at 4mV/ºC/Cell...(+/- 96mV per ºC from a 2C
Delta - 48V System) Higher or lower settings may cause incorrect adjustments
in charge voltage. Without a temperature sensor, charge settings must be
adjusted manually based on the battery temperature when in use, not just
ambient temperatures.
TABLE 5: VRLA AGM Charge Voltage
NOTE:
If charger output is 120
Amps max, 120 is used.
T = 0.38 x 830/120 = 2.9 hrs