Rolls Surrette User Manual

25
VRLA ABSORPTION CHARGE TIME
Where : T = 0.42 x C /I
T = ABSORPTION CHARGE TIME
C = 20 hr RATED CAPACITY (total battery bank)
I = Charging Current (Amps) (recommended 20% to 35% of C20 discharge rate)
0.42 = ( 20%/50%) + 5% (5% is added due to losses)
EXAMPLE:
2 strings of 6 Volt S6-460AGM models
20 hr AH rate = 415 AH x (2 strings) = 830 AH
I = 20% of 830 AH = 166 Amps
T = 0.42 x 830/166 = 2.1 hrs
VRLA FLOAT STAGE AND TERMINATION
The charger can maintain the End Amps current indefinitely or until the charger
is shut off or unplugged. This stage is ideal to maintain battery state of charge.
Make sure the temperature compensation is programmed as specified in Table
5 & 7 (-4mV/°C/cell or -2mVF/cell) or manually adjust the voltage setting
for temperatures varying from 25°C (77°F). As the temperature decreases,
the voltage should increase and vice versa. The profile in Table 5 & 7 can be
used with or without the float stage. Without the float stage, recharge can be
terminated based on time (this will need to be determined as it will vary with
depth of discharge and charge current) or percentage recharge (105%-110%).
AGM CHARGE VOLTAGE QUICK REFERENCE
NOTE:
Set the charge voltage at 2.45 volts per cell (VPC) when using
temperature compensation. Higher or lower voltages may cause incorrect
adjustments in charge voltage. If a sensor is not used, you must manually
adjust charging voltages based on the battery temperature when in use,
not just ambient temperatures.
TABLE 5: AGM Charge Voltage
NOTE:
If charger output is
120 Amps max, 120 is used
T = 0.42 x 830/120 = 2.9 hrs