Rolls Surrette User Manual

42
Confirm End Amps is programmed to 2-3% of C/20 (Series 4000) or 2-5%
(Series 4500 & 5000 with Advanced NAM).
• Decrease Bulk/Absorption/Boost Voltage in .2v to .4v volts increments.
Decrease Absorption Time by 15 to 30 minutes increments as necessary.
Clean and inspect all cabling and connections. Physically disconnect cable,
inspect for terminal concaving (Over torqued), grease and re-torque connections.
Specific gravity readings on individual cell(s) in a battery bank with multiple
series strings vary more than .020 while resting at Float voltage. (Ex 1.265,
(1.265, 1.240, 1.265…)
Indicates there may be an imbalance of charge between parallel strings
of batteries.
Disconnect parallel strings and charge each string individually to balance
charging. For systems with more than two parallel strings of batteries you
may find this is necessary 1-2 times a year to maintain balanced charging.
Indicates there may be connection issues within each series connection
or parallel strings.
• Increase Bulk/Absorption/Boost Voltage by 0.2V increments.
Clean and inspect all cabling and connections. Physically disconnect
cable, inspect for terminal concaving (Over torqued), grease and
re-torque connections.
* Specific gravity readings varying more than .030 in multiple strings of
batteries indicates an imbalance of charge. If specific gravity readings
continue to vary after charging each string individually a Corrective
Equalization may be necessary.
Capacity of the battery bank has decreased.
Capacity loss may be due to sulfation. A balance charge and/or
Equalization may be necessary.
Capacity loss may be due to overheating. Verify that temperature sensors
are properly mounted and verify cell temperatures.
• Capacity loss may be due to over-discharging the battery bank.
• Capacity of the battery bank may no longer support an increase in load.