User's Manual

RONDISH STRIP DOOR MONITOR DMS-02
6.3 QUICK PROGRAMMING GUIDE (001/5 – 001/6)
DOOR MONITOR STRIP : QUICK PROGRAMMING GUIDE
Introducton:
On the door strip monitor you can program the following items
1. Set door number on rotary switch 0-15(F) Identifies door number at Central Monitor
NOTE: When two door monitor strips are
used same door it should be set the same
to allow to work together
2. Set area code/number on rotary switch 0-7 Must match the particular Central Monitor
setting. Refer to CMU-02 User Instructions.
Set to zero if want to receive by all CM.
3. Set door "extension" number 0-6 When two, or more monitor strips are used
for the same door. Sets left side to one
and right side to two and so on
by multiple door strips with same door number.
set to zero if only one door strip used.
4. Set door lock/s timer 0-F Sets door lock/s applied timer in intervals
of 5 seconds. NOTE: setting "0" = no
time-out (continuous application of locks
during alarm).
Step 1:
Remove cap at bottom of strip unit at opposite end to magnetic caregiver key alarm reset point
(blue circle).
Step 2:
DRAWING No.
001/5
TITLE
MODEL No.
Quick Programming Procedure
DMS-02
Rotary programming switch
Programme mode button
(press and hold for 3 seconds until "beep" heard)
Slide off cap and slide
out PCB at bottom of monitor strip