NLUO PMC CONTRACTOR
SIGNATURE AND SEAL SIGNATURE AND SEAL SIGNATURE AND SEAL
VRF AIRCONDITIONING UNITS
SPECIFICATION FOR AIR-CONDITIONING WORK
1 OBJECTIVE OF THE SPECIFICATION
This specification is intended to cover the design, manufacture, testing and delivery, duly packed for transport to site,
for complete Air-conditioning work as specified herein after for the Building.
The scope of the specification also includes the complete erection, final check-up, testing and commissioning at the
site of the entire equipments to be supplied under this specification.
2 GENERAL INFORMATION
Proposed to install the VRF/VRV air-conditioning system for air-conditioning of the Building .
2.1 BASIS OF DESIGN
OUTSIDE DESIGN CONDITION
Summer : 100 °F DBT & 82 °F WBT
Inside Design Condition : 24 ±0.5 °C DBT, around 55% RH.
Occupancy : Normal.
Lighting load : 1.0 W/sq.ft