High Pressure Switch, Low Pressure Switch, Fan Motor Safety Thermostat, Inverter Overload Protector, Over Current
Relay, Fusible Plugs, Fuses.
OIL RECOVERY SYSTEM
Each unit shall be equipped, with an oil separator to ensure stable operation with long refrigerant piping.
INDOOR UNIT:
General
The Indoor unit shall be Ceiling mounted Cassette type or Ceiling mounted Ductable Type or Wall Mounted type or other
as specified in BOQ.
These units should be suitable for operation on 220V-240V, Single Phase, 50 Hz AC electric supply.
These units shall have electronic control valves to control refrigerant flow rate in response to load variation in the room.
The address of IDU shall be set automatically in case of individual and group control.
The IDU shall be basically a Fan coil unit suitable for Ceiling/Wall hung type. Each unit shall have Cooling coil, Blower,
Filter, BLDC Motor, Drain pan and accessories. All the IDUs installed to have individual Cordless/Corded Remote
controls.
Indoor unit shall have cleanable type filter to an integrally moulded / moulded plastic frame. The filter shall be slide away
type and neatly inserted.
It shall be possible to clean the filters either with compressed air or water.
The Cooling coil shall have Aluminum fins and copper tubes. The Fan section shall be dual suction, aerodynamically
designed & balanced turbo, multi blade type blower to ensure low noise and vibration free operation and having multiple