TECHNICAL SPECIFICATION FOR FIREFIGHTING
1.1A. ADDRESSABLE FIRE ALARM SYSTEM:
FIRE ALARM CONTROL PANEL:
Analog addressable 2 loop expandable to 4 loop fire alarm control panel. The panel shall have 16 zonal LED indicators,
programmable sounder circuits, programmable inputs, programmable relays, 3A power supply, Large graphic display, Real time
clock, Expandable from 2 to 4 loops, Certified to EN54-2/ EN54-4, Up to 512 additional programmable I/O via HFP I/O
modules, Powerful, network wide cause and effects, Sensitivity adjustment and Drift Compensation, Can be networked with
HFP control panels, Compatible with HFP and HFP AP-CRL, repeaters, Stores 500 last events in event log Dial up modem
connection available, Compact, stylish enclosure, Installer friendly, removable equipment chassis, Different language and
character set variants available, Fully EN54-2 and EN54-4 compliant improved front loading Printer option. Model number is as
specified in the BOQ.
1.2MULTI SENSOR DETECTOR:
Multi- Sensor which is fully compatible with ESP Analogue Addressable Protocol, having removable high performance
chamber with Twin fire LED's allow 360 degree viewing, User selectable modes, Incorporate Optical and Heat elements, lock
mechanism ( sensor to base), Electronically addressed, approved by LPCB & Vds. Pulsing/non-pulsing controlled from panel.
Variable sensitivity. Electronically Addressed. Model number is as specified in the BOQ.
Specification
Operating Voltage: 17 – 41 V dc
Low Power Mode (typ): 120 A
Quiescent Current (typ): 400 A
Alarm Current (controlled by CIE): 9.1 mA (excluding remote indicator)
Transmission Method: Digital Communications Using ESP
Operating Temperature: Range -20 °C to + 60 °C
Operating Humidity: 95%RH - Non Condensing (at 40 °C)
Storage Temperature: Range -30 °C to + 60 °C
Storage Humidity: <80% RH at 60 °C
Colour / Case Material: White / Polycarbonate
Weight (g): 95