Temperature Rating
32° to 140°F (0° to 60°C) during installation
14° to 167°F (-10° to 75°C) during operation
14. Mechanical Test Requirement
Ultimate Breaking Strength > 400 N (90 lb. ft.)
Minimum Bed Radius 25.4 mm (1.0 inch)
15. Electrical Test Requirement
DC resistance <90.38 Ohm per 100M (328 ft.)
DC Resistance Unbalance <5% at 20°C per ASTM D 4566
Mutual Capacitance <5.6 nF per 100M (328 ft.) at 1KHz and 20°C per ASTM D 4566
Characteristic Impedance <5.6 nF per 100M (328 ft.) at 1 kHz and 20°C per ASTM D 4566
Propagation Velocity >62.1 (at 250 MHz), CMR: 70%, CMP: 72%
16. Overhead Fiber Cable Routing Systems
The overhead fiber cable routing system shall be a system of channel, fittings, and brackets designed to segregate, route,
and protect fiber optic and high performance copper cabling. Channel and fittings shall be assembled using pre-assembled
couplers. A selection of spillout options shall be available that easily attach using the vertical tee. Fittings maintain a
minimum 2" bend radius to protect against signal loss due to excessive cable bends. Available system colors shall be
yellow, orange, and black. A full complement of brackets shall be available for attaching system components to ladder rack.
UL Compliant