factor.
18. VOLTAGE: 380/400/415VAC, 3phase+N+PE
19. Regulation: +/-1% for 100% unbalanced load
20 FREQUENCY: 50Hz +/-0.05 % in free running
mode
21. WAVE FROM: True sine wave
22. THD:<=3% for 100% liner load
23. DYNMIC RESPONSE: For 0-100% step load
changed the output shall remain within +/- 5% &
recovery to 100% within 0 sec.
24. CREST FACTOR: 3:1 at 100% non-liner load
25. OVERLOAD CAPACITY: 125% For 10minutes,
150% for 1 minute.
26. Output of UPS should be 1 phases 4wired un
balance type.
BYPASS STATIC SWITCH
27. AUTO TRANSFER AND RETRANSFER: Load
transfer to bypass in cases of fault is cleared. The
transfers automatically once the fault is cleared.
The transfer and retransfer takes place in <5
milisec, in sync mode and < 20milisec, in a sync
mode.
28. STATIC SWITCH RATING: 14 Times rated
current for 10 milisec, 10 times rated for 100
milisec.
29. MAINTENANCE BY PASS SWITCH: 100%
rated make before type switch should be used.