NLUO PMC CONTRACTOR
SIGNATURE AND SEAL SIGNATURE AND SEAL SIGNATURE AND SEAL
Unless otherwise specified all ceiling fans shall be hung not less than 2.75 M (9 ft.) above floor. The suspension and clamp shall
be painted with approved paint without involving extra cost.
13. INSTALLATION OF FLUORESCENT LIGHT FITTINGS :
Where these are suspended from ceiling by two down rods, or fixed to ceiling / beam directly, at least one fixing to the ceiling /
beam shall be made with Mechanical / Metal fasteners. Electrical drill only shall be used while making holes for the fasteners
which shall be capable of sustaining at least 11 kg. of dead weight.
The down rods and accessories shall be painted with approved paint without involving extra cost.
Unless otherwise specified these should be suspended 2.60 m (8’-6”) above the floor.
The Fluorescent light point/ Ceiling fan point and exhaust fan point shall be terminated in a ceiling rose and at the time of
equipment/ fitting installation it is to be connected with the ceiling rose. The connection (supply and erection) is in the scope of
contractor installing the light/fan fittings.
14. INSTALLATION OF EXHAUST FANS :
Exhaust fans shall be fitted by means of rag bolts embedded in the wall. The required holes in the wall shall be made and
finished neatly with cement plaster and brought to the original finish of the wall. All exhaust fan shall be fitted with GI
Louvers at the outer side.
15. INSTALLATION OF SOCKET OUTLETS :
No socket outlet shall be provided in the bath room at the height less than 130 cms. (4’-3”) from the floor.
No switches shall be provided inside the bath rooms, unless approved by the Engineer in charge.
Socket outlet at locations other than bath rooms shall be either 25 cm (10”) or 130 cms (4’-3”) from the floor.
16. INSTALLATION OF ELECTRIC MOTORS :
Electric Motors shall be earthed with 2 numbers of earthing in opposite side. Earth flat is to be brought near the equipment and
then connected by wire rope socketed at the ends.