All three pin 5 Amps plug points and metallic fan regulator cover should be provided with earthing attachment by No. 14
S.W.G. wires, unless specified otherwise.
Three pin 15 Amp power plug point should be provided with earthing attachment by No. 14 SWG G.I. wire, unless specified
otherwise.
For conduits and accessories for distribution wiring should be provided with earthing attachment by number 14 SWG G.I.
wire, unless specified otherwise.
For looping earthing G.I. wire shall be run conduits being fixed with saddles, this wire shall not be normally visible after
installation when run with the conduit. Where the wire has to be ;taken without ;the conduits this will be fixed with āUā nails
at 2ā-0ā intervals.
11. Painting :
Conduit and all conduit fittings and accessories shall be painted with two coats matt paint. Painting of conduits shall be done to
harmonize with colour bearing surface, i.e. wall, joints, trusses etc. after installation and as approved by the Engineer-in-
charge.